Technical Specification
SENSING INPUT
- Voltage:Â Jumper selectable, 100-130 Vac 1-phase or 190-264 Vac 1-phase
- Frequency:Â 50-60 Hz nominal
POWER INPUT
- Voltage:Â 100-264 V ac 1-phase
- Frequency:Â 50-60 Hz nominal
OUTPUT
- Voltage:Â 82 V D.C. @ 200 V A.C. input
- Current:Â 4A continuous, 7.5A transient for 10 seconds
- Resistance:Â 15 ohms minimum (10 ohms min when input volts < 175 ac)
REGULATION
- Accuracy:Â +/- 1.0%
SYSTEM CHARACTERISTICS
- Thermal Drift: 0.03% per °C change in AVR ambient
- Typical System Response:Â AVR response: 20 ms; Field current to 90%: 80 ms; Machine Volts to 97%: 300 ms
- External Voltage Adjustment:Â +/-10% with 1 k-ohm, 1-watt trimmer
- Under-Frequency Protection (UFRO):Â Set point: 94 – 98% Hz
- Build-up Voltage:Â 4 Volts @ AVR terminals
- Analogue Input:Â Max input +/- 5 Vdc; Sensitivity: 1V for 5% Generator Volts (adjustable)
- Quadrature Droop Input:Â 10 ohms burden; Max. Sensitivity: 0.07 A for 5% droop @ 0PF
- Over-Excitation Protection:Â Set point 75 V dc; Time delay 10-15 seconds (fixed)
ENVIRONMENTAL
- Vibration:Â 20-100 Hz (50mm/sec); 100Hz – 2kHz (3.3g)
- Operating Temperature: -40 to +70°C
- Relative Humidity: 95% (0-70°C)
- Storage Temperature: -55 to +80°C